| Lutron seeTouch QS 2-Button IR Remote Control Raise/Lower Wallstation Features |
| Lutron seeTouch QS 2-Button Wallstation has 2 buttons, IR Remote Control, plus Raise and Lower buttons for lighting and shading control and 2 contact closure input connections |
| Often used in entryways or whole functions to select 1 Scene On and All Off plus Master Raise/Lower |
| Use with Lutron Grafik Eye QS light scene and shading controllers |
| Power up to 3 seeTouch QS wallstations directly off 1 Lutron Grafik Eye QS unit. To power 12 additional Wallstations use Auxiliary Power Supply - TU240-15DC-9-BL |
| Backlit buttons with optional engraving make it easy to find and operate the Wallstation in low light conditions |
| Optional button engraving is angled up to the eye for easy reading |
| Non-Insert Frame version |
| Light Control Features |
| Recalls preset light levels for two scenes (1 and Off; 9 and 10; or 13 and 14). |
| Each button will toggle a zone or a group of zones |
| Starts or stops one sequence (Scenes 5 through 16 sequence) |
| In Panic Mode: Enables or disables Wallstations and makes lights go to Scene 16 |
| Master raise/lower brightens or dims all lighting in the last selected light scene |
| Recalls preset light levels for 4 scenes plus Off with 4-scene IR Wireless Remote Control (GRX-IT) |
| Recalls preset light levels for 8 scenes plus Off with 8-scene IR Wireless Remote Control (GRX-8IT) |
| Contact Closure Features |
| Receives up to two contact closure inputs via a connector on the back of the seeTouch QS wallstation |
| When keypad is programmed as scene, panic, zone toggle or sequence, input 1 closure will perform the top button action, and input 2 closure will perform the bottom button action |
| When the wallstation is programmed as a partition control, input 1 and input 2 closures will close the partition, and input 1 and input 2 openings will open the partition |
| When the wallstation is programmed to fine-tune, input 1 controls raising (closure = start; opening = stop) and input 2 controls lowering (closure = start; opening = stop) |
| Sivoia QS Shade Control Features |
| Used to control multiple groups of shades independently from a single-gang keypad (e.g., a window with a sheer shade and a blackout shade) |
| Pressing the Open (or Close) button once will cause the window treatments to move to their fully open (or closed) position. Tap any button (regardless of function) to stop a shade that is in motion |
| Master raises/lower opens and closes all assigned shades in the last selected scene |
| Control shades with IR Wireless Remote Controls; SVQ-3PIT, SVQ-OCIT, SVQ-4GD-OCIT, and SVQ-4S2G-IT. |